| SPECIFICATIONS 
 Internal Channel: 1
 Temperature Accuracy:
 ±0.5°C(0 to 50°C), ±0.9°F (32 to 122°F)
 Temperature Resolution: 0.05°C
 Temperature Range:
 -20 to 60°C (-4 to 140°F)
 Thermocouple Channels: 8
 Thermocouple Input Types:
 J, K, T, E, R, S, B, N
 Thermocouple Connection:Subminiature female jack
 Cold Junction Compensation:Automatic, based on internal channel
 Maximum Thermocouple Resistance:
 1000Ω, 100Ω recommended
 External Thermocouple Channel
 Accuracy* (Uniform 20°C InternalTemperature):
 J, K, T, E, N: ±0.5°C
 R, S, B:  ±2.5°C
 Resolution:
 J, K, T, E, N: 0.1°C
 R, S, B:  0.5°C
 Temperature Types and Ranges:
 Type J: -210 to 760°C(-346 to 1400°F)
 Type K: -260 to 1370°C(-436 to 2498°F)
 Type T: -260 to 400°C(-436 to 752°F)
 Type E: -260 to 980°C(-436 to 1796°F)
 Type R: -50 to 1760°C(-58 to 3200°F)
 Type S: -50 to 1760°C(-58 to 3200°F)
 Type B: 60 to 1820°C(140 to 3308°F)
 Type N: -260 to 1300°C(-436 to 2372°F)
 
 
 *accuracy does not include errors due to thermocouple
 |  | 
 Memory: 500,000 readings/channel(channels can be disabled to increase memory)
 Temperature Calibration:Digital calibration is availablethrough software
 Calibration Date: Automaticallyrecorded within device to alert userwhen calibration is required
 Recording Interval: 4/sec to 1/dayselectable in software
 Start Time: Start time and date areprogrammable through software
 Real Time Recording: Devicemaybe used with PC to monitor andrecord data in real time
 Power: 9V lithium battery (included)or external power via included acadaptor, data logger switches tobattery power if ac power is lost
 Battery Life (@ 25°C and 10 minrecording interval):
 OM-CP-OCTTEMP-A:18 months typical;
 OM-CP-OCTTEMP2000:18 months typical with displayand blacklight off, 4 monthstypical with continuous displayuse (backlight off)
 Time Accuracy: ± 1 minute/monthwhen RS-232 port is not in use
 Data Format: Date and timestamped, °C, °F, °K, °R, mV
 Computer Interface: PC serial,RS232C COM or USB (interfacecable required); 115,200 baud
 Software: XP SP3/Vista/7 and 8(32-bit and 64-bit)
 Operating Environment:-20 to 60°C (-4 to 140°F)
 5 to 95% RH non-condensing
 Dimensions:
 OM-CP-OCTTEMP-A;
 68 H x 183 W x 32 mm D(2.7 x 7.24 x 1.26"):
 OM-CP-OCTTEMP2000;
 68 H x 183 W x 36 mm D(2.7 x 7.24 x 1.39")
 Weight:OM-CP-OCTTEMP-A; 490 g (17.3 oz)
 OM-CP-OCTTEMP2000: 480 g (16.9 oz)
 Material: Black anodized aluminum
 |