Your Source for Process Measurement & Control
UK
44-796-072-6366
Germany
49-178-631-1266
Product Groups
AC Powered DC Input DIN Rail Signal Conditioner
TRODEKS Engineering | Thermocouples, Pressure Transducers, Flow Meters, PID Controllers
DRI-DC
PLACE ORDER 
  • Field Configurable Input/Output Ranges
  • 1800 Vdc Isolation
  • Touch Calibration Technology
  • High Density DIN Rail Mounting
  • Universal AC Power 85 to 265 Vac
 Specs
 Manuals (contact with email : [email protected])
 Print
Description

Description

The model DRI-DC is an AC powered, DIN rail mount,DC input signal conditioner, with 1800 Vdc isolationbetween input, output and power. It provides a fullyisolated DC output signal in proportion to a DC input.The field configurable input and output feature offersflexible, wide ranging capability for DC current andvoltage signals.

Using a pushbutton instead of potentiometers,improvements in calibration resolution and reliability arerealized due to the elimination of the potentiometers’mechanical variability. The thermal drift and mechanicalvariability of the potentiometers has been removed andreplaced with a digitally stable circuit. Additionally, theinherent zero and span interactivity of analog amplifiercircuitry is removed, providing 100% non-interactiveadjustment.

The DRI-DC can be field configured for virtually anyDC input to DC output within the limits specified.Calibration utilizes touch calibration technology wherethe user simply configures the input for the current orvoltage range via switches, then follows the calibrationprocedure. The output is set by adjusting the input untilthe desired output is present and then pressing theCAL button to store the output level.

The DRI-DC has three diagnostic LEDs. The green(RUN) LED is used for diagnostics to indicate thatpower is on. It will flash quickly if the input signal isabove the calibrated range or slowly if the input signalis below range. It is on continuously when the unit isfunctioning within the calibrated range.

The DRI-DC can be configured for input ranges from10 mV to 100 V or 1 mA to 100 mA, with >90% inputoffset or will adjust down to <10% of full scale inputspan (except on 20 mV/2 mA range where maximumoffset or gain adjustment is 50%). The factory defaultconfiguration for the DRI-DC is:

Input Range: 20 mA (current on)
Input Configuration: Unipolar
Calibrated Input: 4 to 20 mA
Operation: Direct (reverse off)
Calibrated Output: 4 to 20 mA

Specifications
INPUT

Voltage Input:
    Range: 20 mV, 50 mV, 100 mV, 200 mV, 500 mV, 1V, 2V,5V, 10V, 25V, 50V, 100V (dip-switch selectable)
    Impedance: ≥100 kΩ
    Overvoltage: 200V continuous
Current Input:
    Range: 2 mA, 5 mA, 10 mA, 20 mA, 50 mA, 100 mA(dip-switch selectable)
    Impedance: 20 Ω typical
    Overcurrent: 170 mA, protected by self-resetting fuse
    Overvoltage: 60V
Pushbutton Adjustment (Inputs >10 mV):
    Effective Zero Offset: ≥90%
    Effective Span Turn Down: ≥90% except 20 mV/2 mA range in which 50% is max zero offset and span turndown
OUTPUT
Voltage Output:

    Range: 0 to 5V, 0 to 10V (dip-switch selectable)
    Source Impedance: <10 Ω
    Drive: 10 mA max
Current Output:
    Range: 4 to 20 mA, 0 to 1 mA, 0 to 20 mA (dip-switch selectable)
    Source Impedance: >100 kΩ
    Compliance:
        0 to 1 mA: 7.5V max (7.5 kΩ)
        4 to 20 mA: 12V max (600 Ω)
        0 to 20 mA: 12 V max (600 Ω)
Output Ripple:
    <50% Offset or Span Adjust: <0.1% of full scale span or 25 mV RMS, whichever is greater
    >50% Offset or Span Adjust: <0.2% of full scale span or 50 mV RMS, whichever is greater
Output Accuracy:
>2 mA / >20 mV Input Spans: ±0.1% of full-scale inputtypical, ±0.2% maximum
<2 mA / <20 mV Input Spans: ±0.35% of full scale input typical, ± 0.5% maximum including linearity, repeatability and hysteresis @ 23°C
Response Time: 200 msec, typical
Stability: ±0.025% of full scale/°C, maximum for full scale and zero
Common Mode Rejection: 120 dB at DC, >90 dB at 60 Hz
Isolation: ≥1800 Vdc or peak AC between input, output, power and channel-to-channel
ESD Susceptibility: Capable of meeting IEC 801-2 level 3 (8 kV)
Humidity (Non-Condensing):
    Operating: 15 to 95% RH @ 45°C (113°F)
    Soak: 90% RH for 24 hours @ 60°C (140°F)
Temperature:
    Operating: 0 to 55°C (32 to 131°F)
    Storage: -25 to 70°C (-13 to 158°F)
Power: 100 to 240 Vac, ±10%, 50 to 400 Hz; 2.5 W max
Wire Terminals: Socketed screw terminals for 12 to 22 AWG
Weight: 227 g (0.5 lb)
Anemometer  |   Automation  |   Accelerometers  |   Calibrator  |   Cartridge Heaters  |   Chart Recorders  |   Cryogenics  |   Custom Pressure Transducers  |   Data Loggers  |   Data Acquisition  |   Dial Thermometers  |   Fiber Optics  |   Fiber Optic Temperature Measurement  |   Flexible Heaters  |   Flow Meters  |   Glass Bulb Thermometers  |   Grippers  |   Heaters  |   Humidity Measurement  |   Integrated Circuit Sensors  |   Immersion Heaters  |   Infrared Thermometers  |   Level Measurement  |   Load Cells  |   M12 Temperature Connectors  |   Magnetic Flow Meter  |   Panel Meter  |   PID Controllers  |   pH meter  |   Pressure Gauges  |   Pressure Transducers  |   Pressure Transmitters  |   Rotameters  |   RTD  |   Remote Process Monitoring  |   Sanitary Sensors  |   Signal Conditioners  |   Stepper Motors  |   Strain Gages   |   Strip Heaters  |   Temperature Controllers  |   Temperature Labels  |   Temperature Measurement  |   Temperature Sensor Manufacturing  |   Temperature Sensors  |   Temperature Transmitters  |   Thermal Imagers  |   Thermistors  |   Thermocouple  |   Thermocouple Wire | Thermowell  |   Ultrasonic Flow Meters  |   Vortex Flow Meter  |   Wireless Sensors
trodeks.comtrodeks.com - فقخیثنس.زخئ - صصص.فقخیثنس.زخئ