Your Source for Process Measurement & Control
UK
44-796-072-6366
Germany
49-178-631-1266
Thermocouple Input Socket Mount Signal Conditioner
SMSC-TC
PLACE ORDER - Provides Isolated, Linearized DC Output in Proportion to Thermocouple Input
- Field Configurable Thermocouple Types
- Eliminates Ground Loops
- Thermocouple Burnout Detection
- Wide-Ranging 50% Zero and Span Adjustability
- ASIC Technology for Enhanced Reliability
Description
Description
The SMSC-TC isolating thermocouple conditioneroffers wide ranging input and output capability. TheSMSC-TC can be field configured by the user to acceptinput from thermocouple Types J, K, T, E, R, S, and Band to provide current or voltage output. The output islinearized to temperature according to the particularthermocouple type.
The SMSC-TC is a three-port industrial isolator—theoutput is optically isolated from the input up to 1500 V,and both input and output are transformer isolatedfrom the line power. Isolation allows the noise reductionbenefits of grounded thermocouples to be realizedwithout creating ground loop problems and it providesfaster response. The SMSC-TC utilizes the latest inadvanced analog/digital signal processing technology.In addition to its multiple microprocessors, it employsspecial ASIC circuitry for high accuracy and reliability.
The SMSC-TC is equipped with cold-junctioncompensation (CJC) circuitry to provide icepointreference. Upscale, downscale or disabledthermocouple burnout detection is switch selectable.
The SMSC-TC is useful in any application requiring anisolated DC output from a thermocouple input. Typicalapplications include energy management and dataacquisition of process temperatures. The output of theSMSC-TC can drive a digital meter for direct displayor interface with a computer for monitoring and controlapplications.
Model SMSC-TC is equipped with top-mounted LEDsfor INPUT (green), TROUBLE (yellow) and CAL OK(yellow). At start-up, both the INPUT and the CAL OKLEDs light up momentarily for 1 second. Afterwards,these LEDs flash alternately for 10 seconds whilestartup takes place.
The input LED is a diagnostic tool. It remainscontinuously lit if the measured temperature is withinthe selected range of the thermocouple. However, ifthe measured temperature is outside the full rangeof the thermocouple (for example, for a Type J belowminus 200°C or above 750°C), the LED will flash at arate of 4 or 8 Hz for under/over range, respectively. Ifthe thermocouple is within the full temperature range,but outside the selected sub-range (for example, if aType J thermocouple is set for a range of 375 to 500°Cand the temperature is either below 375°C or above500°C) the LED will flash at 0.5 or 1 Hz respectively.
The CAL OK LED is continuously on when the deviceis properly storing the factory calibration referencevoltage. The TROUBLE LED is off during normaloperation of the device.
A major advantage of the SMSC-TC is its wide rangingcapabilities and ease of configuration. The SMSC-TCenables 50% input zero and span adjustability withinthe selected sub-range.
For example for Type E thermocouple range from-18 to 125°C, since the span can be contracted by50%, this enables an input span as narrow as 50%of 143, or 72°C. This span can then be positionedanywhere within the temperature range and can havea zero step-up as large as 50% of the full scale range(e.g. span can start as high as 53°C).
The factory default configuration for the model SMSC-TC is as follows:
Input: Type J
Range: 0 to 500°C (32 to 932°F)
Output: 4 to 20 mA
Burn Out: Upscale
Specifications
INPUT
Ranges: Field configurable, see table
Impedance: >1 MΩ
Input Bias Current (Burnout Detection): <1.5 µA
Overvoltage: ±10V differential
Common Mode (Input to Ground): 1500 Vdc or peak AC, max
Zero and Span Range:
Zero Turn-Up: 0 to 50% of full scale range
Span Turn-Down: 100 to 50% of full scale range
OUTPUT
Voltage Output (Dip-Switch Selectable):
Ranges: 0 to 5 V, 0 to 10 V
Impedance: <10 Ω
Drive: 10 mA max (1 kΩ min)
Current Output (Dip-Switch Selectable):
Ranges: 0 to 1 mA, 4 to 20 mA
Impedance: >100 kΩ
Compliance: 10 V max (500 Ω max @ 20 mA)
Response Time (10 to 90%): 500 mSec, typical
Stability: ±0.04%/°C of full scale range
Isolation: 1500 Vdc or peak AC between input, output and power
ESD Susceptibility: Meets IEC 801-2, Level 2 (4 kV)
Common Mode Rejection: DC to 60 Hz: 120 dB
LED Indicators:
Trouble LED: Yellow - off during normal device operation
Input LED: Green - continuously on if input is withinselected range, flashes otherwise
CAL OK LED: Yellow - continuously on in normal deviceoperation
Thermocouple Burnout Detect: Field-configurable Upscale or Downscale, or disabled
Humidity (Non-Condensing):
Operating: 25 to 95% RH @ 45°C (113°F)
Soak: 90% RH for 24 Hours @ 65°C (149°F)
Temperature Range:
Operating: 0 to 60°C (32 to 140°F)
Storage: -15 to 75°C (5 to 167°F)
Power:
Consumption: 3 W typical, 5 W max
Standard: 120 Vac ±10%, 50 to 60 Hz
Optional: 240 Vac
Weight: 282 g (0.62 lb) Anemometer | Automation | Accelerometers | Calibrator | Cartridge Heaters | Chart Recorders | Cryogenics | Custom Pressure Transducers | Data Loggers | Data Acquisition | Dial Thermometers | Fiber Optics | Fiber Optic Temperature Measurement | Flexible Heaters | Flow Meters | Glass Bulb Thermometers | Grippers | Heaters | Humidity Measurement | Integrated Circuit Sensors | Immersion Heaters | Infrared Thermometers | Level Measurement | Load Cells | M12 Temperature Connectors | Magnetic Flow Meter | Panel Meter | PID Controllers | pH meter | Pressure Gauges | Pressure Transducers | Pressure Transmitters | Rotameters | RTD | Remote Process Monitoring | Sanitary Sensors | Signal Conditioners | Stepper Motors | Strain Gages | Strip Heaters | Temperature Controllers | Temperature Labels | Temperature Measurement | Temperature Sensor Manufacturing | Temperature Sensors | Temperature Transmitters | Thermal Imagers | Thermistors | Thermocouple | Thermocouple Wire | Thermowell | Ultrasonic Flow Meters | Vortex Flow Meter | Wireless Sensors