Your Source for Process Measurement & Control
UK
44-796-072-6366
Germany
49-178-631-1266
Product Groups
AC Powered DC Input DIN Rail Limit Alarm
TRODEKS Engineering | Thermocouples, Pressure Transducers, Flow Meters, PID Controllers
DRI-DC-LA
PLACE ORDER 
  • Field Configurable Input Ranges
  • Touch CalibrationTechnology
  • Setpoints Programmable HI or LO and Failsafe or Non-Failsafe
  • Provides Relay Contact Closures at a Preset DC Input Level
  • Universal AC Power 85 to 265 Vac
  • 24 Vdc Transducer Excitation
  • ASIC Technology for Enhanced Reliability
  • DIN Rail Mounting
 Specs
 Manuals (contact with email : [email protected])
 Print
Description

Description

The DRI-DC-LA is a DIN rail mount, DC voltage orcurrent input limit alarm with dual setpoints and twocontact closure outputs. The field configurable inputand alarm functions offer flexible setpoint capability.Input voltage spans from 10 mV to 200 V and inputcurrent spans from 1 mA to 100 mA can be fieldconfigured. Bipolar inputs are also accepted.

The DRI-DC-LA is configurable as a single or dualsetpoint alarm, with HI or LO trips and failsafe ornon-failsafe operation. Also included are adjustabledeadbands (up to 100% of full scale input) for eachsetpoint, a 24 Vdc voltage source (isolated from linepower) for transducer excitation, and a universal ACpower supply which accepts any voltage between85 and 265 Vac.

The DRI-DC-LA has simplified setpoint calibration.Using a pushbutton instead of potentiometers,improvements in calibration resolution and reliability arerealized due to the elimination of the potentiometers’mechanical variability.

For calibration, simply input the signal level of thedesired trip and press the pushbutton to store it innon-volatile memory. Deadband is entered the sameway with another pushbutton press to store.

The DRI-DC-LA is equipped with three front panelLEDs. The green LED is a dual function LED labeledIN, which indicates line power and input signal status.Active AC power is indicated by the illuminated LED. Ifthis LED is off, check AC power and wiring connections.If the input signal is 7% above or below the configuredinput range the green LED will flash at 8 Hz or 4 Hz,respectively.

The two red LEDs indicate the relay state of eachsetpoint. An illuminated red LED indicates the trippedcondition for the respective setpoint.

The DRI-DC-LA is equipped with two SPDT (formC) relays, rated at 120 Vac or 28 Vdc at 5 A. Each ofthese relays is independently controlled by the fieldconfigurable setpoint and deadband.

The DRI-DC-LA limit alarm setpoints can beconfigured for HI or LO, failsafe or non-failsafeoperation. Each of the setpoints has a respective HIor LO deadband. In a tripped condition, the setpoint isexceeded and the appropriate red LED will illuminate.The trip will reset only after the process falls belowthe HI deadband or rises above the low deadband.For proper deadband operation, the HI setpoint mustbe set above the LO setpoint. In failsafe operation,the relay is energized when the process is belowthe HI setpoint or above the LO setpoint (oppositefor nonfailsafe). In the failsafe mode, a power failureresults in an alarm state output.

Circuitry in the DRI-DC-LA prevents false tripsby repeatedly sampling the input. The input mustbe beyond the setpoint for 100 milliseconds,uninterrupted, to qualify as a valid trip condition.Likewise, the input must fall outside the deadband andremain there for 100 milliseconds to return the alarmto an untripped condition. This results in a “dynamicdeadband” —based on time— in addition to the normaldeadband.

Unless otherwise specified, the factory presets the DRI-DC-LA as follows:
Input: Current
Range: 0 to 20 mA
Output: Dual, SPDT
Trip:
A: HI, B: LO
Failsafe: No
Deadband: (A, B): 0.25%

When switching inductive loads, maximum relay life andtransient EMI suppression is achieved by using externalprotection. Place all protection devices directly acrossthe load and minimize lead lengths. For AC inductiveloads, place a properly rated MOV across the load inparallel with a series RC snubber. Use a 0.01 to 0.1 mFpulse film capacitor (foil polypropylene recommended)of sufficient voltage, and a 47 Ω, ½ W carbon resistor.For DC inductive loads, place a diode across the load(PRV > DC supply, 1N4006 recommended) with (+) tocathode and (-) to anode (the RC snubber is an optionalenhancement).

Specifications
Voltage Input (Unipolar or Bipolar):

    Range: 10 mV, 20 mV, 50 mV, 100 mV, 200 mV,500 mV, 1V, 2V, 5V, 10V, 20V, 50V, 100V, 200V (dip-switch selectable)
    Impedance: >100 kΩ
    Overvoltage: 200 Vrms max
Current Input (Unipolar or Bipolar):
    Range: 1 mA, 2 mA, 5 mA, 10 mA, 20 mA, 50 mA,100 mA (dip-switch selectable)
    Impedance: 20 Ω typical
    Overcurrent: 170 mA rms max
    Overvoltage: 60 Vdc (self-resetting fuse)
    Common Mode (Input to Gnd): 1800 Vdc max
LED Indicators:
    Input (Green): >110% input: 8 Hz flash; <10% input: 4 Hz flash
    Setpoint (Red):
    Tripped: Solid red
    Safe: Off
Limit Differential (Deadband):
    >50 mV/5 mA: 0.25 to 100% of span
    <50 mV/5 mA: 1 to 100% of span
Response Time:
    Dynamic Deadband: Relay status will change whenproper setpoint/process condition exists for 100 msec
    Normal Mode (Analog Filtering): <250 msec (10 to 90%)
Setpoints:
    Effectivity: Setpoints are adjustable over 100% of theselected input span
    Repeatability (Constant Temp): >50 mV/5 mA: 0.1% offull scale; <50 mV/5 mA: 0.2% of full scale
Temperature Stability: +0.05% of full scale/°C max
Excitation Voltage: 24 Vdc, 20 mA max
Common Mode Rejection: DC to 60 Hz: 120 dB
Isolation: 1800 Vdc between contacts, input and power
ESD and Transient Susceptibility: Meets IEC 801-2, Level 3 (8 KV)
Humidity (Non-Condensing):
    Operating: 15 to 95% RH @ 45°C (113°F)
    Soak: 90% RH for 24 hours @ 65°C (149°F)
Temperature Range:
    Operating: 0 to 55°C (32 to 131°F)
    Storage: -25 to 70°C (-13 to 158°F)
Power: 100 to 240 Vac ±10%, 50 to 400 Hz; 2.5 W max
Relay Contacts: 2 SPDT (2 form C) relays (1 relay per setpoint)
    Current Rating (Resistive): 120 Vac, 5A; 240 Vac, 2A; 28 Vdc, 5A
    Material: Gold flash over silver alloy
    Electrical Life: 105 operations at rated load (external relay contact protection is required for use with inductive loads)
    Mechanical Life: 107 operations
Wire Terminations: Screw terminations for 12 to 22 AWG
Weight: 254 g (0.56 lb)
Anemometer  |   Automation  |   Accelerometers  |   Calibrator  |   Cartridge Heaters  |   Chart Recorders  |   Cryogenics  |   Custom Pressure Transducers  |   Data Loggers  |   Data Acquisition  |   Dial Thermometers  |   Fiber Optics  |   Fiber Optic Temperature Measurement  |   Flexible Heaters  |   Flow Meters  |   Glass Bulb Thermometers  |   Grippers  |   Heaters  |   Humidity Measurement  |   Integrated Circuit Sensors  |   Immersion Heaters  |   Infrared Thermometers  |   Level Measurement  |   Load Cells  |   M12 Temperature Connectors  |   Magnetic Flow Meter  |   Panel Meter  |   PID Controllers  |   pH meter  |   Pressure Gauges  |   Pressure Transducers  |   Pressure Transmitters  |   Rotameters  |   RTD  |   Remote Process Monitoring  |   Sanitary Sensors  |   Signal Conditioners  |   Stepper Motors  |   Strain Gages   |   Strip Heaters  |   Temperature Controllers  |   Temperature Labels  |   Temperature Measurement  |   Temperature Sensor Manufacturing  |   Temperature Sensors  |   Temperature Transmitters  |   Thermal Imagers  |   Thermistors  |   Thermocouple  |   Thermocouple Wire | Thermowell  |   Ultrasonic Flow Meters  |   Vortex Flow Meter  |   Wireless Sensors
trodeks.comtrodeks.com - فقخیثنس.زخئ - صصص.فقخیثنس.زخئ